Cummins Power Generation A044Z055 Details and Specifications
Cummins Onan Connect Series Auxiliary Configurable Signal Inputs/Relay Outputs | Part A044Z055
Description: The PowerCommand AUX101 Input/Output module provides up to eight (8) Form-C relay output sets and eight (8) descrete/analog inputs for auxiliary control and monitoring of the power system. The relays may be configured individually from the genset control operator interface or using InPower Software. Module is compatible with genset controls supporting a PCCNet Network and require a twisted pair connection.
Features:
Up to eight (8) configurable Form-C relays provide easy control of system equipment such as lamps, louvers, motors, and pumps. LED status of each relay.
Up to Eight (8) configurable discrete inputs for monitoring equipment status and faults. Equipment status and faults will be annunciated.
Up to Eight (8) Analog inputs. Analog inputs can be assigned one of seven preprogramed functions: Oil temperature, exhaust temperature, fuel level, ambient temperature, alternator RTD, Speed bias, voltage bias.
Two Status LAED's: DS1 (green) indicates the AUX101 is connected to the network and operating normally, DS2 (red) indicates the AUX101 has lost its connection or is not connected to the network.
Device Number Indicator. Seven segment LED used to uniquely define more than one AUX101 on the same network.
May be connected at any point in the PCCNetwork network.
Plug-and-Play networking - No binding required!
Pluggable terminal blocks allow easy one-time wiring.
Less wiring makes installation and system upgrades quick and easy.
UL Listed and Labeled: CSA certified; CE Compliant
5.90"L x 5.30"W x .51"D
Kit Includes: Input/Output Card, Protection Cover, Circuit Card Harness, Generator Electrical Harness,